You are here:

140 Failsafe

Current to pressure, (I/P) electronic converter

Technical features

Medium

Oil free, dry media, min filtered to 50 μm; internal in-built filter

Output pressure

0,2 … 1 bar (3 … 15 psi)
0,2 … 2 bar (3 … 30 psi)

Supply pressure

1,2 … 10,3 bar (18 … 150 psi)

Flow capacity

up to 300 NL/min

Air Consumption

< 2,5 NL/min at 50% signal

Linearity independent

Typically <0.1%, guaranteed <0.2%

Hysteresis & deadband

Typically <0.1%, guaranteed <0.2%

Response time

<1 second (from 0 … 90% or 90 … 10% of output pressure into a 0,5 litre load)

Temperature sensitivity

Typically <0,06% span/°C between
-40 … +85°C (-40 … +185°F)

Supply sensitivity

<0,1% of span for full supply pressure range

Port sizes

Main ports: G1/4 or 1/4 NPT
Integral gauges: G1/4 or 1/4 NPT
Exhaust port: 1/8 NPT

Ambient/Media Temperature

Air supply must be dry enough to avoid ice formation at temperatures below +2°C (+35°F).I.P.

Mounting position

Integral bracket allows for flat surface or 2” (50 mm) pipe mounting in any orientation.
Designed for mounting with 57 … 73 mm pitch U bolts

Materials

Body: aluminium and zinc diecasting
Diaphragms: NBR
Black epoxy powder coating standard