140 Failsafe
Current to pressure, (I/P) electronic converter
Technical features
Medium | Oil free, dry media, min filtered to 50 μm; internal in-built filter |
---|---|
Output pressure | 0,2 … 1 bar (3 … 15 psi) |
Supply pressure | 1,2 … 10,3 bar (18 … 150 psi) |
Flow capacity | up to 300 NL/min |
Air Consumption | < 2,5 NL/min at 50% signal |
Linearity independent | Typically <0.1%, guaranteed <0.2% |
Hysteresis & deadband | Typically <0.1%, guaranteed <0.2% |
Response time | <1 second (from 0 … 90% or 90 … 10% of output pressure into a 0,5 litre load) |
Temperature sensitivity | Typically <0,06% span/°C between |
Supply sensitivity | <0,1% of span for full supply pressure range |
Port sizes | Main ports: G1/4 or 1/4 NPT |
Ambient/Media Temperature | Air supply must be dry enough to avoid ice formation at temperatures below +2°C (+35°F).I.P. |
Mounting position | Integral bracket allows for flat surface or 2” (50 mm) pipe mounting in any orientation. |
Materials | Body: aluminium and zinc diecasting |